av超碰在线观看-小视频成人-毛片av免费观看-国产精品99久久久久久宅男-91色交视频-久久久亚洲天堂-欧洲黄视频-婷婷色网站-超碰人人草-十二月综合缴缴情小说-香蕉茄子视频-日日操天天爽-黄色三级小视频-亚洲网中文字幕-亚洲综合字幕-一区二区福利-日韩精品免费一区二区

POSITION:HOME > QUESTION

QUESTION

Analysis of common faults in the operation of brazed plate heat exchanger

1. Seepage leakage of plate heat exchanger
Because the plate heat exchanger has a long sealing perimeter and a thinner plate, it may show a leaking appearance during the application process. Leakage appearance can be divided into two conditions: internal leakage and external leakage.
A, check whether the import parameters of the hot and cold medium are consistent with the original planned value. If it does not match, you should try to adjust to the original value. If the import parameters have been changed and cannot be adjusted to the original planned value, the planning and accounting should be carried out from the beginning, and the heat exchange area should be increased or decreased or the process combination should be changed.
Analysis of common failures in brazed plate heat exchangers when brazing plate heat exchangers are running
B, if the import parameters of the cold and hot medium are consistent with the original planned value, and the export parameters do not reach the planned value, then stop, open the view board for blockage or slab knot Scale and other conditions, and timely disposal.
a, open the plate heat exchanger, remove the dirt on the surface of the plate, dry it and assemble the heat exchanger from the head. A water pressure test with a pressure of 0.2 to 0.3 MPa was performed on one side. After the slip line is discharged to the other side, the experiment is terminated, the heat exchanger is turned over, and the untested side of the pure water machine sheet is carefully observed, and the wet sheet is a sheet having holes or cracks.
b, in the field can also be used to see through the light, color, to find the waste sheet.
2, plate plate misalignment in plate heat exchanger
About the medium flow and pressure changes, and is a multi-pass combination, long-term use of plate heat exchangers, easy to miss the surface of the plate dislocation. After the plate is misplaced, it sometimes appears to be leaky; some, although not immediately leaking, is a danger of seizure, so it must be disposed of in time. The main causes of misalignment are: deformation of the heat exchanger plate; the gasket of the plate heat exchanger slides away from the gasket groove. To dispose of this misalignment, the deformed plate and the gasket sliding off the gasket groove should be replaced in time.
3. Simple disposal method of plate heat exchanger when there is no maintenance equipment on site
In the application process of the plate heat exchanger, whether it is deformation, crack, perforation of the plate, the gasket is aging and cracking, and all need to be replaced in time. If the sliding line is a spare part that is not satisfied by the site, and the heat exchange equipment has neither spare parts nor downtime, it should be handled on the spot. The method of simple disposal on site is to take out the damaged plate and the plate leaking from the attacking biosafety cabinet in pairs (A plate + B plate). If the number is not too much, the number of flow channels to be cut is not much, after assembling Continuous use has little impact on production.
2019/05/11 09:30:32 5758 Click

肃南| 金川县| 建湖县| 丹东市| 南和县| 许昌县| 杭锦旗| 哈密市| 余庆县| 建昌县| 云龙县| 双城市| 察雅县| 三门县| 祁连县| 潍坊市| 石河子市| 西华县| 平凉市| 龙游县| 成都市| 丹阳市| 年辖:市辖区| 会宁县| 永善县| 鄂温| 杭锦后旗| 古蔺县| 舟曲县| 开鲁县| 兰西县| 青阳县| 清丰县| 丰都县| 措勤县| 安义县| 阳东县| 沙雅县| 清水河县| 乐至县| 讷河市|